Signet 2552 Metal Magmeter
*3-2552.090*
3-2552.090 Rev E 07/10 English
English
SAFETY INSTRUCTIONS
1. Depressurize and vent systems without Hot-tap valve prior to installation or removal.
2. Con rm chemical compatibility before use.
3. Do not exceed maximum temperature/pressure speci cations.
4. Wear safety goggles or face shield during installation/service.
5. Do not disassemble or alter product construction.
6. Disconnect power before attempting any service or wiring.
2. Speci cations
1. Description
The Signet 2552 Metal Magmeter from Georg Fischer features all-stainless steel construction. The PVDF nosepiece and FPM O-rings
are the only other wetted materials. The 2552 installs quickly into standard 1¼ in. or 1½ in. pipe outlets, and is adjustable to t pipes
from DN50 to DN2550 (2 to 102 inches). Three sensor lengths allow maximum exibility to accommodate a variety of hardware
con gurations, including ball valves for hot-tap installations.
When equipped with the frequency output, the 2552 is compatible with any Signet ow instrument, while the S
3
L Digital output enables
multi-channel compatibility with the Signet 8900 Multi-Parameter Flow Controller. Select the blind 4 to 20 mA current output to interface
directly with dataloggers, PLCs or telemetry systems.
Key features include Empty Pipe Detection, LED-assisted troubleshooting, and Bi-Directional span capability (in 4 to 20 mA models).
The Signet 3-0250 USB to Digital (S
3
L) Con guration/Diagnostic Tool is available to customize every performance feature in the 2552
so it can be adapted to the user's application requirements.
Performance
Pipe size range: DN50 to DN2550 (2 in. to 102 in.)
Flow Range:
Minimum: 0.05 m/s (0.15 ft/s)
Maximum: 10 m/s (33 ft/s) for pipes to DN 1200 (48 in.)
3 m/s (10 ft./s) for pipes over DN 1200 (48 in.)
Linearity: ±(1% reading + 0.01 m/s)
±(1% reading + 0.033 ft/s)
Repeatability: ±0.5% of reading @ 25 °C
Accuracy: ±2% of measured value (in reference conditions
where the uid is water at ambient temperature, the sensor
is inserted at the correct depth and there is a fully developed
ow pro le which is in compliance with ISO 7145-1982 (BS
1042 section 2.2))
Minimum Conductivity: 20 S/cm
Wetted Materials
316L Stainless Steel body and electrodes
• PVDF Insulator
• O-rings: FPM (standard)
Cable: 4-cond + shield, PVC jacket (Fixed cable models) or
Water-resistant rubber cable assembly with Turck
®
NEMA 6P
connector
Power Requirements
4 to 20 mA: 24 VDC ± 10%, regulated, 22.1 mA maximum
Frequency: 5 to 24 VDC ± 10%, regulated, 15 mA maximum
• Digital (S
3
L): 5 to 6.5 VDC, 15 mA maximum
Reverse polarity and short circuit protected
Cable Options
Fixed 7.6 m (25 ft) cable
Detachable water tight sensor cable with Turck
®
connector
sold separately, two lengths: 4m (13 ft) or 6m (19.5 ft)
Custom lengths available, contact Georg Fischer Signet
Electrical
Current Output (4 to 20 mA)
Programmable and reversible
Factory Range: 4 to 20 mA = 0 to 5 m/s
• Loop Accuracy:
32 A max. error (@ 25 °C @ 24 VDC)
Temp. drift: ±1 A per °C max.
Power supply rejection: ±1 A per V
Isolation: Low voltage < 48 VAC/DC from electrodes and
auxiliary power
Maximum cable: 300 m (1000 ft)
Max. Loop Resistance: 300
Error condition: 22.1 mA
Frequency output
Compatible with Signet 5075, 5500, 5600, 8550 and 8900
Max. Pull-up Voltage: 30 VDC
Short Circuit Protected: 30 V @ 0 pull-up for one hour
Reverse Polarity Protected to -40 V for 1 hour
Overvoltage Protected to +40 V for 1 hour
Max. Current Sink: 50 mA, current limited
Maximum cable: 300 m (1000 ft)
Digital (S
3
L) Output
Compatible with Signet 8900
Serial ASCII, TTL level 9600 bps
Maximum cable: Application dependent (See 8900 manual)
Standards and Approvals
• CE
U.S. Patent No.: 7,055,396 BI
NEMA 4 (IP65) ( xed cable models)
NEMA 6P (IP68) (Submersible cable models only)
Signet recommends maximum 3 m. (10 ft) submersion depth
for maximum 10 days continuous submersion.
Manufactured under ISO 9001 and ISO 14001
China RoHS (Go to www.gfsignet.com for details)
Vista de página 0
1 2 3 4 5 6 ... 15 16

Resumo do Conteúdo

Página 1 - Signet 2552 Metal Magmeter

Signet 2552 Metal Magmeter*3-2552.090*3-2552.090 Rev E 07/10 EnglishEnglishSAFETY INSTRUCTIONS1. Depressurize and vent systems without Hot-tap valv

Página 2

10 2552 Magmeter Pipe Size (ANSI)ScheduleOD (Inches)WALL (Inches)ID (Inches)H Dim -2 VersionH Dim mm-3X VersionK-FactorPulse/literK-FactorPulse/GalFa

Página 3 - 3. Selecting a Location

112552 Magmeter8.1 Bi-Directional FlowThe 2552 magmeter is designed to measure bi-directional fl ow.• 4 to 20 mA output models: May be scaled to span

Página 4 - 4 2552 Magmeter

12 2552 Magmeter • Conductivity is less than 20 S/cm.• Electrical noise• Electronic component failure.• 4 to 20 mA is not scaled same as Loop dev

Página 5 - 52552 Magmeter

132552 MagmeterSensor Selection GuideThe 2552 Magmeter can be installed into a variety of pipe sizes. Follow the steps below to ensure that you choos

Página 6 - 2. Prepare the pipe:

14 2552 Magmeter Notes:

Página 8 - 8550-1 Flow Transmitter

Georg Fischer Signet LLC, 3401 Aerojet Avenue, El Monte, CA 91731-2882 U.S.A. • Tel. (626) 571-2770 • Fax (626) 573-2057For Worldwide Sales and

Página 9

2 2552 Magmeter 2.1 Temperature and Pressure Specifi cationsMax. Temperature/Pressure RatingStorage Temperature: -15 °C to 70 °C (5 °F to 158 °F) i

Página 10 - -3X Version

32552 Magmeter3. Selecting a LocationThe 2552 requires a fully developed turbulent fl ow profi le for accurate measurement. Selecting the correct locat

Página 11 - 112552 Magmeter

4 2552 Magmeter 4. General Installation and Grounding Tips4.1 Sensor conditioningThe Magmeter output signal may be unstable immediately after instal

Página 12 - 12 2552 Magmeter

52552 Magmeter1. The height from the magmeter electrodes to the alignment rod is: -2 Versions: 276.3 mm ( 10.88 in. ) -3 Versions:

Página 13 - 132552 Magmeter

6 2552 Magmeter 3. Install the Magmeter into the pipea. Apply sealing tape or paste to the male threads of the process connector nut.b. Tighten th

Página 14 - 14 2552 Magmeter

72552 Magmeter Pipe Top ViewAlign Magmeter with pipe ±1° H FLOW → FLOW → 4. Adjust the magmeter position and insertion deptha. Insert the brass rod

Página 15 - 152552 Magmeter

8 2552 Magmeter • The 2552 outputs an open collector frequency signal that can be connected to any powered Signet fl ow meter. (Models 5075, 5500, 56

Página 16 - Ordering Information

92552 Magmeter7. Calibration Data7.1 K-factors and Full Scale Current Values for 3-2552-2x - x - xx and 3-2552-3x - x - xx MagmetersPipe Size (ANSI)S